Home / PLC

Moog IMI220-420A001 Analog Input Module

Moog

M400 Series

4 Analog Input 
PRODUCT DESCRIPTION

The IMI220-420A001 module is used to control 8 12 bit analog inputs with a working range from 0 to +10V. The inputs are of differential type to guarantee a high degree of immunity from disturbances; the voltages read on the input are transformed into quote.

Two interrupt quote can be defined for each input (one quota for the greater than or equal to comparison and the other for the less than or equal to): the operating system automatically returns the state of the greater than or equal to and less than or equal to markers for the entered quote.

 

External coding: 7, 9, 10.

Connection: by means of: IMI220-420A001 (20 pin 5.08 mm connector).

Use: more than one IMI220-420A001 module can be installed on the bus; this module can be optional.

Configuration parameters: module code and revision, identifier.

 

Characteristics of the module


STATIC CHARACTERISTICS

 

Number of inputs

8 differential

Input resistance

10 MΩ

Input range

 

- voltage

0...+10 V

- current

1 µA

Vref outputs

 

- voltage

10 V

- accuracy

± 0.1 %

- current (max)

50 mA

- short circuit protection

yes

Galvanic separation

no

Analog input Error

 

- maximum error @ 25°C

36 mV @ FS

- temperature coefficient

500 µV/°C

Maximum error over full temperature range

20 mV

Digital resolution

12 bit

Data format returned to the application program

INT

Value of LSB

2.45 mV

Maximum permanent allowed overload

30 V

Digital output reading under overload condition

FS value (saturation)

Type of input

differential

Common mode characteristic

 

- d.c.

60 dB

- 50 Hz

60 dB

- 60 Hz

60 dB

   

DYNAMIC CHARACTERISTICS

 

Total system transfer time

250 µs

Sample duration time

200 µs

Sample repetition time

user-programmable (min. time slice)

Input filter characteristics

 

- type

low pass

- order

1st

- transition frequency

120 Hz

   

GENERAL CHARACTERISTICS

 

Conversion method

successive approximations

Operating mode

according command

Type of protection

RC

Supply current

 

- +5 V

50 mA

- +15 V

10 mA

- -15 V

10 mA

Common points between channels

Vref, 0V15

Front connector

20 pins M, pitch 5.08 mm

Cables section

 

- material

copper

- clamping range (min/max)

0.08...2.5 mm²

- rigid H05(07) V-U

0.5...2.5 mm²

- flexible H05(07) V-K

0.5...2.5 mm²

- flexible with terminal according to DIN 46228/1

0.5...2.5 mm²

- flexible with insulating collar according to DIN 46228/4

0.5...1.5 mm²

Terminal arrangements

4 + 4 differential inputs

Effect of incorrect input terminal connection

none

Operating temperature

 

- in vertical position

0...60° C

- in horizontal position

0...40° C

Dimensions L x H x D (mm)

25 x 130 x 95

Weight

0.150 Kg

   

MISCELLANEOUS CHARACTERISTICS

 

Crosstalk between channels

 

- d.c.

63 dB

- 50 Hz

63 dB

- 60 Hz

63 dB

Repeatability at fixed temperature after  specified stabilization time

0.075% FS