The IMI220-405A001 power supply module generates the current necessary for the functioning of the modules installed on the bus. The module operates on a 24 VDC current. The IMI220-405A001 module is able to supply the following voltages:
+5 V voltage to supply the main processor;
+/-15 V voltage necessary for the functioning of the analog modules;
On this module there is a buffer battery necessary for the maintaining of the data in the main processor module RAM.
Coding external: 1, 4.
Connection by means of: IMI220-405A001 (5 pin, 5.08 mm).
Use: only one IMI220-405A001 module can be installed on the bus.
Characteristics of the module
Input voltage |
|
- nominal value |
24 VDC |
- range |
- 10%...+20% |
Reverse polarity protection |
yes |
Input current @ 24VDC |
|
- max |
1 A |
- min |
- |
Efficiency |
83% tip. |
Effect of incorrect connections of power to the supply(ies): |
|
- reverse polarity |
none |
- improper voltage level and/or frequency |
<15 V -> OFF, >42 V -> inner fuse blows off |
- improper lead connection |
- |
Max interruption time (1) |
1 ms |
Output voltages |
|
- digital power |
5 VDC |
- analog voltage |
+ 15 VDC (± 5%) |
- analog voltage |
- 15 VDC (- 10%...+ 5%) |
Output current |
|
- +5 V |
1.7 A |
- +15 V |
+ 0.3 A |
- -15 V |
- 0.3 A |
Short circuit protection |
electronic |
PLC behaviour for typical power up/down sequences |
depend on program |
Backup Battery |
lithium (3.6 V - 0.75 Ah) |
- life |
5 years at 25°C |
OK relay |
|
- type |
single contact N/O |
- breaking capacity |
400 mA @ 125 VAC / 1 A @ 30 VDC |
Operating Diagnostics |
|
- low batt. |
red led |
-- voltages OK |
green led |
Front connector |
5 pole M, pitch 5.08 mm |
Cables section |
|
- material |
copper |
- clamping range (min/max) |
0.08...2.5 mm² |
- rigid H05(07) V-U |
0.5...2.5 mm² |
- flexible H05(07) V-K |
0.5...2.5 mm² |
- flexible with insulating terminal according to DIN 46228/1 |
0.5...2.5 mm² |
- flexible with insulating collar according to DIN 46228/4 |
0.5...1.5 mm² |
Operating temperature |
|
- in the vertical position |
0...60° C |
- in the horizontal position |
0…40° C |
Dimensions L x H x D (mm) |
25 x 130 x 95 |
Weight |
0.200 Kg |