Home / PLC

Moog IMI220-418A001 Digital Output

Moog

M400 Series

12 Pin Digital Output
PRODUCT DESCRIPTION

The IMI220-418A001 module is a peripheral unit used to control sixteen 24 VDC 1 A digital outputs protected against short circuit, over temperature and open circuit; the outputs are divided into two groups of 8. In the case of a short circuit or over temperature occurring on any of the 16 outputs, the module switches off the output in question, signals the event by means of switching on the front red LED of the group to which the output belongs puts all the 8 alarm variables of the same group to the value TRUE 1.

 

Coding: external: 8, 9, 10.

Connection: by means of: IMI220-418A001 (20 pin, 5.08 mm).

Use: more than one IMI220-418A001 module can be installed on the bus; this module can be optional.

Configuration parameters: module code and revision, identifier.

 

Characteristics of the module


Output circuits

12 (source)

In groups of

2

Type of output

PNP

Load voltage

+ 24 VDC

- range

± 20%

Output current

 

- for each channel (max)

2 A

- total (max)

24 A

- for group (max)

4 A

- OFF level

25 µA

Protection

 

- short circuit

yes

- short circuit current

9 A (0.3 A in protected over temperature)

- over temperature

yes

- open circuit

yes

- reverse polarity

yes

- protection restoring

automatic

Voltage limitation

 

- for inductive loads (typ.)

- 1 VDC

Galvanic separation

no

Output delay time TQD

 

- from "0" to "1"

50 µs

- from "1" to "0"

50 µs

Output delay time TQT

 

- from "0" to "1"

150 µs

- from "1" to "0"

150 µs

Common points between channels

0V24

Suppressor network against voltage peaks due to inductive

kickback

passive clamp

Effects of incorrect output terminal connection

protected against sc. at 24V and 0V24

Output behaviour during

 

- MPU interruption

automatic turn off

- voltage drop

the output follows the power voltage down to 4V,then it turns off

- voltage interruptions

turn off

- power up/down seq.

up/down

Way of operation

non-latching

Effects of multiple overloads on multi-circuit modules (twice Inom)

none

Visual indicator

 

- outputs (load side)

12 green led

- alarm

1 red led

Front connector

20 pins M, pitch 5.08 mm

Cables section

 

- material

copper

- clamping range (min/max)

0.08...2.5 mm²

- rigid H05(07) V-U

0.5...2.5 mm²

- flexible H05(07) V-K

0.5...2.5 mm²

- flexible with terminal according to DIN 46228/1

0.5...2.5 mm²

- flexible with insulating collar according to DIN 46228/4

0.5...1.5 mm²

Cables length

 

- shielded

500 m

- not shielded

250 m

Supply current

 

- typical

60 mA

Operating temperature

 

- in vertical position

0...60° C

- in horizontal position

0...40° C

Dimensions L x H x D (mm)

25 x 130 x 95

Weight

0.180 Kg